acuitybrands nlight_eclypse_system_controller_firmware 不安全的默认资源初始化

admin 2023-11-30 19:44:31 Ali_nvd 来源:ZONE.CI 全球网 0 阅读模式
acuitybrands nlight_eclypse_system_controller_firmware 不安全的默认资源初始化

CVE编号

CVE-2021-40825

利用情况

暂无

补丁情况

N/A

披露时间

2021-09-18
漏洞描述
nLight ECLYPSE (nECY) system Controllers running software prior to 1.17.21245.754 contain a default key vulnerability. The nECY does not force a change to the key upon the initial configuration of an affected device. nECY system controllers utilize an encrypted channel to secure SensorViewTM configuration and monitoring software and nECY to nECY communications. Impacted devices are at risk of exploitation. A remote attacker with IP access to an impacted device could submit lighting control commands to the nECY by leveraging the default key. A successful attack may result in the attacker gaining the ability to modify lighting conditions or gain the ability to update the software on lighting devices. The impacted key is referred to as the SensorView Password in the nECY nLight Explorer Interface and the Gateway Password in the SensorView application. An attacker cannot authenticate to or modify the configuration or software of the nECY system controller.
解决建议
建议您更新当前系统或软件至最新版,完成漏洞的修复。
参考链接
https://insights.acuitybrands.com/psirt-blog-2369078/nlight-eclypse-default-k...
https://www.acuitybrands.com/products/detail/588952/nlight/necy-system-contro...
受影响软件情况
# 类型 厂商 产品 版本 影响面
1
运行在以下环境
系统 acuitybrands nlight_eclypse_system_controller_firmware * Up to (excluding) 1.17.21245.754
运行在以下环境
硬件 acuitybrands nlight_eclypse_system_controller - -
CVSS3评分 8.6
  • 攻击路径 网络
  • 攻击复杂度 低
  • 权限要求 无
  • 影响范围 已更改
  • 用户交互 无
  • 可用性 无
  • 保密性 无
  • 完整性 高
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:H/A:N
CWE-ID 漏洞类型
CWE-1188 不安全的默认资源初始化